Low Temperature Depth Waste Heat Utilization Technology

According to the national thirteen five energy-saving emission reduction planning, waste heat utilization is an important project in a longer period of time in China. At present, waste heat utilization mainly applied in below field:1. Thermal power plants and similar energy companies such as low temperature waste heat Economizer and MGGH; 2 industrial kiln enterprises waste heat power generation and the original waste heat boiler waste heat utilization 3. Iron and steel enterprises waste heat power generation and the original waste heat boiler heat utilization. Hengtao Energy Conservation Environmental Protection Co., Ltd. has engaged in long-term waste heat Power generation and low temperature waste heat utilization and developed unique characteristics of Hengtao waste heat utilization technology.

Main technical features:

1, reasonable material - anti-corrosion

For the low temperature economizer and MGGH in the flue gas cooler and flue gas reheater, based on the flue gas acid dew point, selecting the ND steel, 316L, 2205 and other steel; air preheater and garbage power plant or biological power plant GGH , Choose single-sided enamel tube or double-sided enamel tube.

2, flue gas inlet optimization - anti-bias flow

It is important to install a suitable flue gas reflux device in the flue gas inlet to establish a reasonable flue gas flow field to ensure the uniformity of the flue gas flow rate. When the flue gas flow rate is reasonable, most of the heating surface wear is caused by the local high flow rate.

3, flue gas flow optimization - anti-wear, anti-fouling

The main measures to reduce and prevent wear is to select the appropriate flue gas flow rate, low temperature flue gas self-cleaning flow rate of 8m / s or more, our company's H-fined tube low temperature heat exchanger generally choose flue gas flow rate 8-10m / s; air preheater flue gas side flow rate of 8-12m / s, air side flow rate of 12m / s below.

4, other

There are always various situation occur during boiler operation, we will confirm boiler operation plan based on different flue gas conditions,  arranging experienced professional engineer to design heat exchanger for the implementation of the final technical transformation effect.

5, the case

Case 1: Zhengzhou Taixiang 135MW unit MGGH,

Flue gas cooler inlet flue gas volume: 508000nm3 / h, inlet flue gas temperature: 125 ℃, outlet flue gas temperature: 95 ℃

Circulating water: 203t // h, inlet water temperature: 75 ℃, outlet water temperature: 100 ℃;

Flue gas reheater inlet flue gas: 538000nm3 / h, inlet flue gas temperature: 46 ℃, outlet flue gas temperature: 75 ℃

Circulating water: 203t // h, inlet water temperature :, 100 ℃, outlet water temperature: 75 ℃;

Reflected by the user: good effects in practice

Case 2: Datang Suihua 2x350MW unit low temperature economizer,

Pre-cooler inlet flue gas volume: 1189326nm3 / h, inlet flue gas temperature: 145 ℃, outlet flue gas temperature: 110 ℃

After the cooler inlet flue gas: 1265095nm3 / h, imported flue gas temperature: 104 ℃, the export of flue gas temperature: 98 ℃

Reflected by the user: good effects in practice